Implemented MIB Description

Standard RF1213

Definition

OID

returned message

iso.org.dod.internet.mgmt.mib-2.system.sysDescr

1.3.6.1.2.1.1.1

MICROLAN Temperatue
OCT_STRING

iso.org.dod.internet.mgmt.mib-2.system.sysObjectID

1.3.6.1.2.1.1.2

NULL

iso.org.dod.internet.mgmt.mib-2.system.sysUpTime

1.3.6.1.2.1.1.3

upTime [TimeTicks]

iso.org.dod.internet.mgmt.mib-2.system.sysContact

1.3.6.1.2.1.1.4

M-TECH www.dcf.sk

iso.org.dod.internet.mgmt.mib-2.system.sysName

1.3.6.1.2.1.1.5

NULL

iso.org.dod.internet.mgmt.mib-2.system.sysLocation

1.3.6.1.2.1.1.6

user defined Location in Telnet

 

 

 

 

 

 

 

 

MIB - MTECH definitions

Definition

OID

returned message

.numsensors

.1316.55.1.0

number of active sensor READ ONLY

.intTemperature

.1316.55.2.1.1.x

x=1..16

temperature in INTEGER * 10 in Celsius,

241 =  24.1C

.stringTemperature

.1316.55.2.1.2.x

x=1..16

Temperature in OCTET STRING format

Example:
"+24.1C"

 

.statusSensor

.1316.55.2.1.3.x

Temperature sensor status

INT32

0 = OK
1
=  no sensor
2= CRC error on sensor

.nameSensor

.1316.55.2.1.4.x

Sensor name  x

x= 1..16

READ ONLY

.tempLOLimits

.1316.55.2.1.5.x

Low temperature limit for sensor x

x= 1..16
.
READ ONLY

.tempHILimits

.1316.55.2.1.6.x

High temperature limit for sensor x

x=1..16

 

 

TRAP messages: Specific Trap

Enterprise OID: 1.3.6.1.4.1.1316.55

OID bindings:

1.3.6.1.4.1.1316.55.3.T

 

T

OID

description

.devlocation

.1

SNMP adapter name

Configurable in telnet  sysname

.sensorName

.2

Sensor name

.tempValue

.3

INTEGER temperature value
 

141  =  14.1'C

.sensorStatus

.4

Sensor Status

0 = OK
1 = CRC ERROR
2= No device